by Paolo Sandri, STMicroelectronics, Santa Clara, Calif., How2Power Today, May 15 2020
Focus:
To deliver power more efficiently in data centers, rack bus bar power distribution is moving
from 12 V to 48 V (54 V nom.) to lower distribution losses. This requires developing new
topologies to efficiently manage the conversion from the 54-V/48-V bus and “smoothly merge”
with the current 12-V ecosystem. This article presents details of ST’s Stacked Buck topology
(STB), which steps down 48 V to a regulated 12 V with high-efficiency and high-density. This
article explains the principles of operation and guidelines for designing and customizing the
STB for an application’s specific power needs. That includes stacking of cells, to accommodate
lower voltage MOSFETs, or adding cells in parallel for higher current output, enabling it to
deliver from 500 W up to 3.2 kW.